ShuntCoilMV

Medium-voltage shunt coil with reactive absorption modeling.

Supports shunt reactor analysis with configurable reactive power absorption for voltage control and Ferranti effect mitigation in balanced three-phase MV distribution networks.

Inherits from: ExtrasNotesMixin, HasPresentationsMixin

Import

python
from pyptp.elements.mv import ShuntCoilMV

Properties

PropertyTypeRequiredDefaultDescription
generalGeneralYes-
presentationslist[ElementPresentation]Yes-
extraslist[Extra]No[]
noteslist[Note]No[]

General

Core electrical and operational properties for MV shunt coils.

Encompasses connection node, reactive power rating, nominal voltage, earthing configuration, and reliability statistics.

PropertyTypeRequiredDefaultDescription
nodeGuidNoNIL_GUID
guidGuidNo(auto UUID)
creation_timefloatNo0.0
mutation_dateintNo0
revision_dateintNo0
variantboolNoFalse
namestrNo""
switch_stateintNo0
field_namestrNo""Name of the connection field.
failure_frequencyfloatNo0.0Mean number of occurrences that the coil fails (short circuit) per year.
repair_durationfloatNo0.0Mean duration of repair or replacement in minutes.
maintenance_frequencyfloatNo0.0Mean number of occurrences that the coil is in maintenance per year.
maintenance_durationfloatNo0.0Mean duration of maintenance in minutes.
maintenance_cancel_durationfloatNo0.0Mean duration of cancellation of maintenance in case of emergency in minutes.
not_preferredboolNoFalse
QfloatNo0.0Reactive power in Mvar.
unomfloatNo0.0Nominal voltage in kV.
profileGuidNoUUID(...)Name of the coil power profile.
earthingintNo0Star point earthing setting (0=no, 1=yes).
refloatNo0.0Earthing resistance with earthed star point in Ohm.
xefloatNo0.0Earthing reactance with earthed star point in Ohm.
earthing_nodeGuid | NoneTypeNoNone
voltage_controlboolNoFalseIndicates whether the voltage control has been switched on or off.
u_onfloatNo0.0Voltage above which the shunt reactor switches off in kV.
u_offfloatNo0.0Voltage under which the shunt reactor switches on in kV.